Fire performance power cable to BS6837 suitable as fire alarm cable and emergency lighting cable
Name | Description | Material |
---|---|---|
Conductors | It is the current carrying component of the cable. | Plain annealed stranded class 2 conductor to BS EN 60228 |
PRIMARY INSULATION | The rated voltage level of the cable depends on the dielectric strength and thickness of the insulation | Mica Glass tape |
SECONDARY INSULATION | Extruded XL-LSZH compound |
IEC 61034 & BS EN 50268: | Low smoke emission |
BS 6387: | Fire resistance C-W-Z test for small sizes |
IEC60331-21: | Fire resistance C-W-Z test for small sizes |
IEC 60754 & BS EN50267: | Acid gas emission |
Voltage Rating: | 600/1000 Volts |
Fire resistance: | C-W-Z test as per BS 6387 for small sizes and IEC60331-21 for large sizes which cannot fit in a conduit. Cables comply IEC 6033121 fire test at increased temperature of 950°C which is higher than that specified by the standard. |
Cable Operating temperature: | Maximum 90°C |
Short circuit temperature: | Maximum 250°C |
Minimum Bending Radius: | 12 x Cable diameter |
1 core | Red, Black, Yellow, Blue, Green/Yellow. (Other Color as per specified standard can also be manufactured) |